Schneider Electric
C40N32D400 ComPacT NSX400N 400 A 3P 50 kA Molded Case Circuit Breaker | Schneider Electric
C40N32D400 ComPacT NSX400N 400 A 3P 50 kA Molded Case Circuit Breaker | Schneider Electric
20 en existencias
No se pudo cargar la disponibilidad de retiro
The Original New Schneider Electric C40N32D400 ComPacT NSX400N is a three-pole molded case circuit breaker (MCCB) designed for electrical distribution and circuit protection in industrial and commercial power systems. Rated at 400 A at 40°C, it operates at voltages up to 690 V AC and provides reliable protection against overloads and short-circuit faults.
Equipped with an electronic MicroLogic 2.3 trip unit, the circuit breaker provides adjustable long-time overload protection, adjustable short-time short-circuit protection, and fixed instantaneous short-circuit protection. Its 3P3D configuration provides protection on all three poles, while the adjustable long-time current setting ranges from 160 A to 400 A.
The NSX400N offers a rated ultimate short-circuit breaking capacity (Icu) of 50 kA at 380/415 V AC, 42 kA at 440 V AC, and 30 kA at 500 V AC under IEC 60947-2. Its high breaking capacity and electronic protection functions make it suitable for demanding electrical distribution applications requiring coordinated circuit protection.
Featuring a fixed mounting arrangement, front-connected terminals, and a toggle operating mechanism, the C40N32D400 supports flexible installation in industrial switchboards and electrical distribution panels. Its compact NSX400 frame provides IP40 protection and IK07 mechanical impact resistance under the specified installation conditions.
The C40N32D400 belongs to the newer-generation Schneider Electric ComPacT NSX range and is suitable for industrial power distribution systems requiring a 400 A electronic circuit breaker with adjustable overload and short-circuit protection.
Core Engineering Highlights:
400 A rated current at 40°C | Three-pole 3P3D configuration | ComPacT NSX400N circuit breaker | MicroLogic 2.3 electronic trip unit | 50 kA Icu at 380/415 V AC | 42 kA Icu at 440 V AC | 30 kA Icu at 500 V AC | 690 V AC rated operational voltage | 800 V AC rated insulation voltage | 8 kV impulse withstand voltage | Adjustable long-time protection 160–400 A | Adjustable short-time protection 1.5–10 × Ir | Fixed instantaneous protection 4,800 A | IP40 protection | IK07 impact resistance | Fixed mounting | Front connection
Key Features:
-
Original New Schneider Electric C40N32D400 ComPacT NSX400N molded case circuit breaker.
-
400 A rated current at an ambient temperature of 40°C.
-
Three-pole 3P3D configuration with protection on all three poles.
-
Electronic MicroLogic 2.3 trip unit for adjustable overload and short-circuit protection.
-
Adjustable long-time current setting from 160 A to 400 A with nine available settings.
-
Adjustable short-time protection from 1.5 to 10 times the long-time current setting.
-
Fixed instantaneous short-circuit protection with a 4,800 A pickup threshold.
-
50 kA ultimate short-circuit breaking capacity at 380/415 V AC under IEC 60947-2.
-
42 kA breaking capacity at 440 V AC and 30 kA at 500 V AC.
-
Rated operational voltage of up to 690 V AC.
-
Rated insulation voltage of 800 V AC and impulse withstand voltage of 8 kV.
-
Thermal memory function retains protection information for 20 minutes before and after tripping.
-
Integrated electronic protection functions cover long-time overload, short-time short-circuit, and instantaneous fault conditions.
-
Green ready-to-operate LED and orange/red overload indicators provide local operating-status information.
-
Fixed mounting arrangement with front-connected electrical terminals.
-
Toggle operating mechanism supports straightforward manual ON/OFF operation.
-
IP40 enclosure protection and IK07 mechanical impact resistance.
-
Suitable for industrial and commercial electrical distribution systems requiring adjustable electronic circuit protection.
Applications:
-
Industrial electrical power distribution systems.
-
Commercial building main distribution boards.
-
Industrial switchboards and electrical control panels.
-
Three-phase feeder circuit protection.
-
Industrial machinery and equipment power distribution.
-
Factory electrical distribution networks.
-
Commercial infrastructure and utility distribution panels.
-
Power distribution systems requiring 400 A circuit protection.
-
Industrial installations requiring adjustable overload and short-circuit protection.
-
Electrical systems requiring high short-circuit breaking capacity.
Technical Specifications:
| Attribute | Specification |
|---|---|
| Catalog Number | C40N32D400 |
| Product Type Designation | ComPacT NSX400N Circuit Breaker |
| Product Family | Schneider Electric ComPacT NSX |
| Product Range | ComPacT NSX400–630 |
| Product Category | Circuit Protection |
| Product Type | Molded Case Circuit Breaker (MCCB) |
| Device Short Name | NSX400N |
| Device Application | Electrical Distribution |
| Rated Current | 400 A at 40°C |
| Number of Poles | 3P |
| Number of Protected Poles | 3D |
| Rated Operational Voltage | 690 V AC |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Utilization Category | Category A |
| Suitability for Isolation | Yes, EN/IEC 60947-2 |
| Trip Unit | MicroLogic 2.3 |
| Trip Unit Technology | Electronic |
| Trip Unit Protection Functions | L / So / I |
| Long-Time Overload Protection | Yes |
| Short-Time Short-Circuit Protection | Yes |
| Instantaneous Short-Circuit Protection | Yes |
| Long-Time Pickup Setting Ir | Adjustable, 9 settings |
| Long-Time Pickup Range | 160–400 A |
| Long-Time Delay | Fixed |
| Long-Time Delay at 1.5 × Ir | 400 seconds |
| Long-Time Delay at 6 × Ir | 16 seconds |
| Long-Time Delay at 7.2 × Ir | 11 seconds |
| Thermal Memory | 20 minutes before and after tripping |
| Short-Time Pickup Setting Isd | Adjustable, 9 settings |
| Short-Time Pickup Range | 1.5–10 × Ir |
| Short-Time Delay | Fixed |
| Instantaneous Pickup Setting Ii | Fixed |
| Instantaneous Pickup Threshold | 4,800 A |
| Earth-Leakage Protection | Not Included |
| Zone Selective Interlocking (ZSI) | Not Included |
| Icu at 220/240 V AC | 85 kA |
| Icu at 380/415 V AC | 50 kA |
| Icu at 440 V AC | 42 kA |
| Icu at 500 V AC | 30 kA |
| Icu at 525 V AC | 22 kA |
| Icu at 660/690 V AC | 10 kA |
| Ics at 220/240 V AC | 85 kA |
| Ics at 380/415 V AC | 50 kA |
| Ics at 440 V AC | 42 kA |
| Ics at 500 V AC | 30 kA |
| Ics at 525 V AC | 11 kA |
| Ics at 660/690 V AC | 10 kA |
| UL Breaking Capacity at 240 V AC | 85 kA |
| UL Breaking Capacity at 480 V AC | 50 kA |
| UL Breaking Capacity at 600 V AC | 20 kA |
| Breaking Capacity Code | N – 50 kA at 415 V AC |
| Rated Insulation Voltage (Ui) | 800 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Operating Mechanism | Toggle |
| Mounting Mode | Fixed |
| Mounting Support | Backplate |
| Mounting Position | Horizontal / Vertical / Flat on Back |
| Terminal Connection | Front Connection |
| Connection Pitch | 45 mm |
| Power Dissipation per Pole | 19.2 W |
| Mechanical Durability | 15,000 operating cycles |
| Electrical Durability at 440 V AC | 12,000 cycles at In/2; 6,000 cycles at In |
| Electrical Durability at 690 V AC | 6,000 cycles at In/2; 3,000 cycles at In |
| Local Signaling | Green Ready LED / Orange 90% Ir LED / Red 105% Ir LED |
| Number of Accessory Slots | 6 |
| Electrical Standard | EN/IEC 60947-2 |
| Dimensions (W × H × D) | 140 × 255 × 110 mm |
| Net Weight | Approximately 6.05 kg |
| Gross Package Weight | Approximately 5.37 kg |
| Package Dimensions (L × W × H) | 292 × 160 × 150 mm |
| EAN / GTIN | 3606482002685 |
| Enclosure Protection | IP40 |
| Mechanical Impact Protection | IK07 |
| Pollution Degree | 3 |
| Overvoltage Category | III |
| Electrical Shock Protection | Class II on Front Face |
| Operating Temperature | -25 to +70°C |
| Storage Temperature | -50 to +85°C |
| Relative Humidity | 0–95% |
| Operating Altitude Without Derating | 0–2,000 m |
| Operating Altitude With Derating | 2,000–5,000 m |
| Total Lifecycle Carbon Footprint | 362 kg CO₂ equivalent |
| Recyclability Potential | 56% |
System Compatibility:
-
Designed for three-phase AC electrical distribution systems.
-
Suitable for industrial and commercial installations requiring circuit protection up to 400 A.
-
Supports electrical networks operating at voltages up to 690 V AC.
-
Three-pole 3P3D configuration provides protection on all three phases.
-
MicroLogic 2.3 electronic trip unit provides long-time, short-time, and instantaneous protection functions.
-
Adjustable long-time current settings allow the protection threshold to be configured between 160 A and 400 A.
-
Adjustable short-time protection supports pickup settings from 1.5 to 10 times the selected long-time current setting.
-
Fixed instantaneous protection operates at a 4,800 A pickup threshold.
-
Thermal memory supports protection coordination by retaining thermal information before and after tripping.
-
Suitable for installation in industrial distribution boards and electrical switchboards with compatible ComPacT NSX400 mounting arrangements.
-
Fixed backplate mounting supports horizontal, vertical, and flat-on-back installation positions.
-
Front-connected terminals support compatible electrical cable and busbar connection arrangements.
-
The six accessory slots provide provisions for compatible circuit-breaker accessories and auxiliary components.
-
Green, orange, and red LED indicators support local monitoring of operating readiness and overload conditions.
-
Suitable for protection coordination with upstream and downstream circuit breakers when the applicable discrimination and selectivity tables are followed.
-
The circuit breaker is suitable for isolation in accordance with EN/IEC 60947-2.
-
Rated short-circuit breaking capacity must be selected according to the prospective fault current at the installation point.
-
The IP40 rating applies to the circuit-breaker assembly under the specified installation conditions; additional enclosure protection may be required for the complete switchboard.
-
Confirm supply voltage, prospective short-circuit current, cable and busbar ratings, trip-unit settings, protection coordination, and installation requirements before commissioning or replacement.
Related Products:
-
LV432598T – Schneider Electric ComPacT NSX400/630 Extended Rotary Handle, 209–600 mm, IP55
-
ComPacT NSX400 Accessories – Schneider Electric Auxiliary Contact and Signaling Accessories
-
ComPacT NSX400 Accessories – Schneider Electric Shunt Trip and Undervoltage Release Accessories
-
ComPacT NSX400 Accessories – Schneider Electric Terminal and Connection Accessories
-
ComPacT NSX400/630 Accessories – Schneider Electric Electrical and Mechanical Operating Accessories
-
ComPacT NSX400 Range – Schneider Electric 3-Pole and 4-Pole Molded Case Circuit Breakers
-
MicroLogic 2.3 – Schneider Electric Electronic Trip Unit for ComPacT NSX Circuit Breakers
PLC ERA is an independent industrial automation distributor supplying genuine Original New products through established global supply channels. All products are factory sealed when applicable and undergo quality inspection prior to shipment. Schneider Electric and ComPacT are registered trademarks of Schneider Electric SE.
Nota: Para garantizar que reciba la cotización más competitiva del momento, le recomendamos que se ponga en contacto con nuestro equipo de ventas. Dado que los precios del mercado se actualizan constantemente, le proporcionaremos la información más reciente. Puede completar el formulario de contacto a continuación y esperar a que nuestro servicio de atención al cliente se comunique con usted, usar el chat en línea en la esquina inferior derecha o hacer clic directamente en " Contactar con el servicio de atención al cliente ".
Compartir